2-staged pressure control system consists of:

  • High pressure regulator with inlet pressure switch for monitoring the pressure status with reduction to an intermediate pressure of 1 … 8 barg
  • Safety valve to protect the low pressure regulator, response pressure 10 barg
  • Solenoid valve DN25, normally open
  • Low pressure regulator for 70 … 110 mbarg outlet pressure
  • Gas extraction up to approx. ≥10.5 barg pressure
  • Assembled and checked ready for installation, including documentation

For Nitrogen
Temperature range -20 … + 40 ° C
Inlet pressure max. 300 barg
Output max. 150 Nm³ / h